For most LED grow lights on 120 V power, a 14 AWG cord handles up to 15 amps over short runs, and a 12 AWG cord handles longer runs and heavier loads. The right size depends on three numbers: total amps, cord length and the breaker on the circuit. This guide shows how to work out each one, with examples for a single light, a full tent and a multi-light room.
In the US, wire is sized with the American Wire Gauge (AWG) system. The number runs backward. A smaller number means a thicker conductor.
Thicker wire has less resistance. Less resistance means less heat and less voltage lost along the run. Grow lights run for 12 to 18 hours a day, so heat in a cord matters more than it does for a tool used for ten minutes.
Most search results for this topic cover landscape lighting or household fixtures. Those use different rules, often low-voltage systems. A plug-in LED grow light runs on 120 V or 240 V mains power, so the numbers below apply to line-voltage wiring and cords.
The wire does not care about lumens or PPFD. It cares about current. Use the actual wall draw printed on the fixture label or spec sheet, not the equivalent wattage on the box.
The formula is simple:
Amps = watts ÷ volts
Worked examples at 120 V:
| Setup | Wall draw | Amps at 120 V | Amps at 240 V |
|---|---|---|---|
| One small light | 100 W | 0.83 A | 0.42 A |
| One light for a 2x4 tent | 240 W | 2 A | 1 A |
| One light for a 4x4 tent | 480 W | 4 A | 2 A |
| One high-output fixture | 720 W | 6 A | 3 A |
| Four 720 W fixtures | 2,880 W | 24 A | 12 A |
Add the fan, the carbon filter fan, the controller and the dehumidifier on the same circuit. In a small tent the light is often only half the load. Our guide to calculating amps and watts for a grow room circuit walks through the full tally.
If you are still choosing fixtures, the LED grow light wattage guide explains how many watts per square foot a space needs. That number sets your amps.

A cord has two limits. One is how much current the copper and jacket can carry. The other is how much voltage the cord loses over its length. Cord charts apply whichever limit is stricter.
One published extension cord chart lists cord ratings of 13 A for 16 AWG, 15 A for 14 AWG and 20 A for 12 AWG. It also notes that a standard household plug caps any cord at 15 amps, whatever the wire size. It applies a 5% voltage-drop budget at 120 V. Its figures by length:
| Cord length | 16 AWG | 14 AWG | 12 AWG | 10 AWG |
|---|---|---|---|---|
| 25 ft | 13 A | 15 A | 15 to 20 A | 20 A+ |
| 50 ft | 10 to 12 A | 15 A | 15 to 20 A | 20 A+ |
| 100 ft | 6 A (light loads only) | about 10 A | 15 A | 20 A |
| 150 ft | Not recommended | about 6 A | about 10 A | 15 to 16 A |
Read the table like this:
The cheapest fix for a voltage problem is a shorter cord. If you need more than 50 feet to reach an outlet, ask whether a new outlet near the grow space is a better answer.
A thick cord does not make a circuit safer. The breaker and the wiring in the wall set the ceiling.
Common pairings in US homes:
The NEC treats a load that runs three hours or more as continuous. Grow lights qualify. A continuous load should not exceed 80% of the breaker rating, as explained for homeowners here. That gives you these limits at 120 V:
| Breaker | Continuous limit (80%) | Watts at 120 V |
|---|---|---|
| 15 A | 12 A | 1,440 W |
| 20 A | 16 A | 1,920 W |
So a 15 amp circuit can feed two 480 W lights and a few small fans. It cannot feed four 720 W fixtures. Those need a 240 V circuit, several 120 V circuits, or fewer lights.
Check what else shares the circuit. Bedroom outlets are often daisy-chained with lighting and other rooms. A hair dryer in the next room can trip a breaker you thought was lightly loaded.
Many commercial-grade LED fixtures accept 100 to 277 V input. At 240 V the same wattage draws half the amps. That means thinner wire, smaller voltage drop and more lights per breaker. Check the fixture label for its input range, and have an electrician install any new 240 V circuit.
Gauge is one part of a safe cord. The U.S. Consumer Product Safety Commission advises checking that a cord is listed by a recognized testing laboratory such as UL, Intertek (ETL) or CSA. The same CPSC notice warns that overheating can happen at the plug, at the socket or along the whole cord.
Use this checklist:
Plug-in timers, controllers and power strips have their own amp ratings. Make sure the rating at least matches the load, since a light-duty strip on a 12 A load becomes the weak link.
Many LED fixtures use a dimming or control line that is separate from the power cord. These carry a signal, not power, so the gauge rules above do not apply to them. What matters is the connector type and the cable length the system supports.
For systems that need them, we stock:
Check each product page for compatibility with your fixture before ordering. Never use a power cord where a control cable is specified, or the reverse.
We sell lights, kits and accessories, and we see the same pattern in support questions. Most cord problems come from long runs and loads that grew over time. A grower starts with one light, adds a second, then a third, and keeps the same 16 AWG cord.
Our advice is short:
Efficiency is also how our supplemental under-canopy lighting is used. It adds light where the canopy shades the lower plant. It is meant to raise yield per watt rather than to raise the total load. Add its amps to your tally like any other fixture.
— Scott
If your wiring is the limit, the fixture is the easiest thing to change. We carry top lighting and under canopy grow lights in a range of wattages. For single-light tents, look at the ThinkGrow LED Model-I or the Model-I Plus. For larger spaces, the ION 720W LED grow light is one option. Check the spec sheet on each page for the exact wall draw before you size cords.
Space is limited? See our small LED grow lights. They draw less current, so they work with ordinary cords and outlets. You can browse the whole range, including tents, kits and environmental controls, on the LED Grow Lights Depot homepage.
| Setup | Typical load | Suggested cord | Circuit |
|---|---|---|---|
| Single small light, under 10 ft | Under 2 A | 16 AWG or thicker | Shared 15 A is fine |
| 2x4 or 3x3 tent, one light plus fans | 3 to 6 A | 14 AWG | 15 A, not shared with heavy loads |
| 4x4 tent with dehumidifier | 6 to 10 A | 14 AWG short, 12 AWG for long runs | 15 A or 20 A, dedicated |
| 5x5 or multi-light room | 12 A and up | Fixed wiring, not cords | Dedicated 20 A or 240 V circuit by an electrician |
These are planning figures based on the chart above, not wiring instructions. Your fixtures, local code and existing wiring decide the final answer.
For a plug-in LED fixture on 120 V, a 14 AWG cord covers most single lights up to 15 amps over runs of about 50 feet. Use 12 AWG for longer runs or heavier loads. Always compute amps from the fixture’s actual wall draw first.
Only for light loads over short runs. The chart above rates 16 AWG at 13 A for 25 feet, and it falls to 6 A at 100 feet. If the cord feels warm, replace it with a thicker one.
At 120 V, the 80% limit for continuous loads is 12 amps, or 1,440 watts. Subtract your fans and other equipment, then divide what is left by the wattage of one light. Two 480 W lights with small fans fit. Four 720 W lights do not.
Not for plugging a light into an existing outlet with a correctly rated cord. You do need a licensed electrician to add outlets, install a 240 V circuit or change breakers. Ask for one before the room’s load goes above what the existing circuit can carry.